Trang chủ / Knowledge / Cold Storage Insulation & Energy Optimization

Cold Storage Insulation & Energy Optimization

Insulation thickness by temperature

Room tempRecommended PU panelNote
+5°C (chiller)80-100 mmDisplay / prep rooms
0°C (fresh)100-120 mmStandard cold store
-18°C (frozen)150-180 mmUse 200 mm in hot climate
-30°C (deep freeze)200 mmBlast / IQF support

Where the energy goes

  • Envelope losses (walls, roof, floor, doors) — the biggest fixed load; fix with right thickness + vapour barrier.
  • Doors & traffic — open doors are the top variable loss; use fast PVC strips, air curtains, dock shelters.
  • Defrost — electric defrost wastes most; prefer hot-gas or pump-down defrost, off-peak timed.

Practical savings

  • LED lighting with motion sensors (vs fluorescent).
  • EC fans on evaporators and condensers (30-50% fan energy).
  • Head-pressure control on condensers to avoid over-cooling at night.
  • Setpoint optimisation: +1°C on a frozen store barely affects safety but cuts load.

Frequently asked questions

Q: Is thicker always better?
A: Up to a point — thicker panel pays back via lower run hours; beyond ~200 mm the extra cost rarely pays in mild climates.

Q: Which defrost is cheapest to run?
A: Hot-gas defrost reuses compressor heat; electric defrost is simplest but most expensive on the bill.