홈 / Knowledge / Refrigerant Leak & GWP Calculation: CO2e Made Simple

Refrigerant Leak & GWP Calculation: CO2e Made Simple

What GWP means

Global Warming Potential (GWP) measures how much heat a refrigerant traps versus the same mass of CO2 over 100 years. CO2 itself = 1. A leak of 1 kg of R134a (GWP 1430) equals 1430 kg of CO2e.

GWP of common refrigerants

RefrigerantGWPClass
R134a1430A1
R410A2088A1
R404A3922A1
R32675A2L
R452A~1140A2L
R454B~466A2L
R290 (propane)3A3
CO2 (R744)1A1

How to calculate your leak impact

CO2e (kg) = annual leak (kg) × GWP. Example: a 50 kg R404A system losing 15% per year leaks 7.5 kg → 7.5 × 3922 = 29,415 kg CO2e. Switching that system to R454B cuts the same leak to 7.5 × 466 = 3,495 kg CO2e — an 88% drop.

How to cut leaked emissions

  • Tighten joints, use brazed/silver connections, pressure-test before charge.
  • Add leak detection on A2L/ammonia systems (also a code requirement).
  • Choose lower-GWP refrigerant where performance allows.
  • Recover and reclaim refrigerant at end of life.

Frequently asked questions

Q: Does a smaller charge always mean lower CO2e?
A: Lower charge helps, but GWP dominates — a tiny R404A charge can beat a large R290 charge only if the R290 is huge. Pick low-GWP first.

Q: Which GWP threshold do rules use?
A: The EU F-Gas phase-down and many importers now steer buyers toward GWP < 750 (A2L) or natural refrigerants (R290/CO2).