Cold Storage Insulation & Energy Optimization
Insulation thickness by temperature
| Room temp | Recommended PU panel | Note |
|---|---|---|
| +5°C (chiller) | 80-100 mm | Display / prep rooms |
| 0°C (fresh) | 100-120 mm | Standard cold store |
| -18°C (frozen) | 150-180 mm | Use 200 mm in hot climate |
| -30°C (deep freeze) | 200 mm | Blast / IQF support |
Where the energy goes
- Envelope losses (walls, roof, floor, doors) — the biggest fixed load; fix with right thickness + vapour barrier.
- Doors & traffic — open doors are the top variable loss; use fast PVC strips, air curtains, dock shelters.
- Defrost — electric defrost wastes most; prefer hot-gas or pump-down defrost, off-peak timed.
Practical savings
- LED lighting with motion sensors (vs fluorescent).
- EC fans on evaporators and condensers (30-50% fan energy).
- Head-pressure control on condensers to avoid over-cooling at night.
- Setpoint optimisation: +1°C on a frozen store barely affects safety but cuts load.
Frequently asked questions
Q: Is thicker always better?
A: Up to a point — thicker panel pays back via lower run hours; beyond ~200 mm the extra cost rarely pays in mild climates.
Q: Which defrost is cheapest to run?
A: Hot-gas defrost reuses compressor heat; electric defrost is simplest but most expensive on the bill.