Refrigerant Leak & GWP Calculation: CO2e Made Simple
What GWP means
Global Warming Potential (GWP) measures how much heat a refrigerant traps versus the same mass of CO2 over 100 years. CO2 itself = 1. A leak of 1 kg of R134a (GWP 1430) equals 1430 kg of CO2e.
GWP of common refrigerants
| Refrigerant | GWP | Class |
|---|---|---|
| R134a | 1430 | A1 |
| R410A | 2088 | A1 |
| R404A | 3922 | A1 |
| R32 | 675 | A2L |
| R452A | ~1140 | A2L |
| R454B | ~466 | A2L |
| R290 (propane) | 3 | A3 |
| CO2 (R744) | 1 | A1 |
How to calculate your leak impact
CO2e (kg) = annual leak (kg) × GWP. Example: a 50 kg R404A system losing 15% per year leaks 7.5 kg → 7.5 × 3922 = 29,415 kg CO2e. Switching that system to R454B cuts the same leak to 7.5 × 466 = 3,495 kg CO2e — an 88% drop.
How to cut leaked emissions
- Tighten joints, use brazed/silver connections, pressure-test before charge.
- Add leak detection on A2L/ammonia systems (also a code requirement).
- Choose lower-GWP refrigerant where performance allows.
- Recover and reclaim refrigerant at end of life.
Frequently asked questions
Q: Does a smaller charge always mean lower CO2e?
A: Lower charge helps, but GWP dominates — a tiny R404A charge can beat a large R290 charge only if the R290 is huge. Pick low-GWP first.
Q: Which GWP threshold do rules use?
A: The EU F-Gas phase-down and many importers now steer buyers toward GWP < 750 (A2L) or natural refrigerants (R290/CO2).