How to Size an Industrial Water Chiller by Cooling Load (200 kW Example)
The core formula
For water, cooling capacity is:
Q (kW) = ṁ (kg/s) × 4.186 × ΔT (K)
where ṁ = volumetric flow ÷ 0.001 m³/kg, and ΔT = supply minus return temperature. In practical units:
Q = flow (m³/h) × 1000 ÷ 3600 × 4.186 × ΔT
Worked example: 200 kW process chiller
- Choose a typical process ΔT of 5 K (supply 7 °C, return 12 °C).
- Required flow = 200 ÷ (4.186 × 5) × 3.6 ÷ 1000 ≈ 34 m³/h.
- Compressor: one 200 kW screw, or 2-3 parallel scroll/Copeland or Bitzer units for redundancy and part-load efficiency.
- Condenser: air-cooled for easy install, water-cooled (with tower) where water is available and ambient is high.
Step-by-step selection
- Find the process heat load from the machine datasheet or measured duty (kW).
- Pick ΔT — 5 K is standard for process water; 3 K for tight-tolerance labs.
- Compute flow with the formula above; size pump and piping for it.
- Choose compressor type — scroll for <100 kW, screw for 100-1000 kW, parallel racks for load swings.
- Select refrigerant — R134a/R513A for stability, R454B for lower GWP.
Frequently asked questions
Q: Why does my chiller deliver less than rated kW?
A: Rating is at 35 °C ambient and nameplate ΔT. Higher ambient, higher return temp, or fouled condenser all cut real capacity.
Q: One big compressor or several small?
A: Several parallel units give redundancy and better part-load efficiency; one screw is cheaper to install for steady duty.