Home / Knowledge / A1 vs A2L Refrigerants: Pipe-Diameter Rules under PED and China TSG

A1 vs A2L Refrigerants: Pipe-Diameter Rules under PED and China TSG

Why refrigerant flammability class drives piping rules

Refrigerants are classed by toxicity and flammability. A1 = non-flammable, low toxicity (e.g. R134a, R410A, CO2). A2L = low flammability with low burning velocity (e.g. R32, R454B, R455A). The class determines how pressure equipment and piping are regulated under the EU Pressure Equipment Directive (PED 2014/68/EU) and China's pressure-pipeline codes (TSG).

PED 2014/68/EU thresholds

A pipe assembly enters PED scope when both diameter and pressure exceed a threshold. For A1 (non-flammable) refrigerant piping the practical entry is roughly DN>32 and PS×DN>1000 (bar·mm). For A2L refrigerants such as R32 the threshold drops to about DN>25. In short, A2L systems cross the PED line at smaller diameters, triggering design, manufacturing and notified-body obligations earlier.

China TSG rules

China's pressure-pipeline code applies above DN≥50 and PS≥0.1 MPa for certain media. A2L's flammability also brings additional safety oversight even below PED-like thresholds, so designers must check both DN and PS against the applicable TSG family (e.g. TSG D0001).

Design impact for exporters

  • Size DN/PS early: an A2L loop can cross a regulatory line that an A1 loop would not.
  • A2L needs tighter joints, leak detection and documented welding where applicable.
  • Document refrigerant class, charge and pressure for customs and compliance files.

FAQ

Q: Is R32 A1 or A2L? A2L (mildly flammable). R134a/R410A are A1.

Q: Does A2L always need PED? Only when DN and PS exceed the A2L threshold (about DN>25).

Q: Which is simpler to certify for export? A1 systems face fewer pressure-equipment hurdles; A2L offers lower GWP at the cost of stricter piping rules.